PLC, I/O & HMI

1756-ENBT

Allen-Bradley

Allen-Bradley 1756-ENBT sourcing reference. Send the complete nameplate details and required quantity for review.

Supply status

This page identifies a sourcing reference. It does not guarantee continuous stock. Availability, condition, quantity, lead time, and commercial terms are confirmed after inquiry.

Copy the model and paste it into WhatsApp with your required quantity.

Reference details

Manufacturer / brand
Allen-Bradley
Model / reference
1756-ENBT
Series / type
Confirm against nameplate
Condition
Confirm with inquiry
Quantity
Confirm with inquiry
Lead time
Confirm with inquiry

Product information

Product Overview

The 1756-ENBT is a first-generation EtherNet/IP bridge module for the ControlLogix 1756 platform — 10/100 Mbps RJ45 interface with 64 TCP connections and 128 CIP connections (64 + 64 CIP unconnected messages per side). Rockwell’s official lifecycle status is Discontinued, with repair options available. It was the standard Ethernet route for 5561/5570-era ControlLogix systems and remains one of the most frequently searched spare-part numbers in the installed base.

Technical Specifications (Official Rockwell Data)

Product family ControlLogix communication module (first-generation EtherNet/IP)
Network EtherNet/IP
Interface 1 × copper RJ45, 10/100 Mbps (Cat 5)
TCP connections, max 64
CIP connections, max 128
CIP unconnected messages 64 + 64 (backplane + Ethernet)
Current draw 700 mA @ 5.1 V DC, 3 mA @ 24 V DC
Power dissipation 3.7 W (12.6 BTU/h)
Operating temperature 0…60 °C (32…140 °F)
Isolation 30 V continuous, basic insulation, Ethernet to backplane
EFT/B immunity ±2 kV @ 5 kHz on Ethernet ports
Lifecycle status (Rockwell) Discontinued; repair options available

Lifecycle Status & Availability

Rockwell officially lists the 1756-ENBT as Discontinued. The active replacement is the 1756-EN2T (double the connection capacity, same slot format). Discontinued status makes the ENBT a high-demand spare part: lines locked to first-generation Ethernet baselines still run millions of these modules worldwide, and buyers typically either source exact-revision spares or plan a controlled upgrade to EN2T.

Typical Applications

  • Emergency replacement for failed Ethernet bridges in 5561/5570-era systems
  • Revision-matched spares where a firmware jump to EN2T would require a controlled change procedure
  • Bridge inventory during staged migrations from ENBT to EN2T/EN4TR

Related & Compatible Models

Direct successor: 1756-EN2T (Active, 128 TCP / 256 CIP). Ring-redundant successors: 1756-EN2TR / EN4TR. Used with ControlLogix 5561/5570 controllers (L6x/L7x families) and compatible with the whole 1756 chassis range.

Requesting a Quotation

For a discontinued module, revision matching is critical. Send a nameplate photo with the full catalog number, series letter and firmware revision, plus quantity. This page carries official Rockwell data only; stock, condition and price are confirmed per quotation.

Frequently Asked Questions

Is the 1756-ENBT discontinued?

Yes — Rockwell’s official lifecycle status is Discontinued (repair options available). The active replacement is 1756-EN2T. Remaining-stock availability is verified per request.

What should I replace it with?

The 1756-EN2T is slot-compatible and doubles connection capacity. For ring-redundant or Gigabit needs, see 1756-EN2TR or 1756-EN4TR. Verify firmware/AOP compatibility with your controller before cutover.

Why would I buy a discontinued module instead of upgrading?

Because many plants freeze Ethernet-bridge firmware baselines: swapping to EN2T can require program-side changes, AOP updates and a validation window. A revision-matched ENBT spare keeps the line running today while the upgrade is scheduled.

How do I confirm which revision I have?

The series letter and firmware revision are printed on the module label. A clear nameplate photo attached to your quotation request is the most reliable way to get a matched unit.

MODEL INQUIRY

Request this
reference.

Include a nameplate photo or full specification when revisions may differ.

For photos or documents, email sales@zhenxinindustrial.com and include your model number.

Submitting does not confirm stock or create an order. We use your details to respond to this inquiry. See our Privacy Policy.